Skip to content
  • Proudly Made in the USA
  • QUOTE
  • 888.653.3333
  • sale@moishaglass.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
    • Specialty Glass
    • Laminated Safety Glass
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Blog
  • Contact
    Contact Us
    Meet Our Team
    Find Your Local Rep
    Request a Quote
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Articles
WIRED GLASS
Letter to UL on Misuse of Wired Glass in Fire Doors
WIRED GLASS

Letter to UL on Misuse of Wired Glass in Fire Doors

ByDiana S
| October 7, 2014

This is a letter from NFPA 80 Chair, John Degenkolb, to UL about his concern about UL’s listing of wired glass in 60 minute applications despite the fact that using wired glass in fire doors is unsafe.

Letter to UL on Misuse of Wired Glass in Fire Doors

J. R. Beyreis
Underwriters Laboratories Inc.degenkob_title
333 Pfingsten Road
Northbrook, IL 60062-2096

Dear Jim:

A problem involving the UL listing of fire-rated glass has been brought to my attention as Chairman of NFPA 80. I am not writing on be-half of that Committee because we have no proposed meeting this year at which it could be discussed.

It seems that UL is listing a glass—probably a ceramic material—as having a 60-minutes listing by UL. The problem is no building code with which I am familiar, has a requirement for 1-hour glass but rather 45-minutes based on the capability of wired glass.

Some years ago the Consumer Products Safety Commission proposed a ban against wired glass when it would be located in a place where impact by a pedestrian was possible. I wrote the CPSC, as Chairman of NFPA 80, stating that there was no satisfactory replacement for wired glass in fire doors and, if its use was prohibited, an increase in the number of injuries could be anticipated. This was in reference to fire-rated wired glass as opposed to architectural wired glass. Since that time new glazing materials have been developed such as Fire Lite, Pyro Swiss and Contraflam. None uses wire and the last name as a clear fire resistive intumescent interlayer between 2 layers of tempered glass. Incidentally, the CPSC did not invoke the ban on wired glass for use in fire doors.

Apparently a glass (other than Contraflam) has been tested successfully by UL for 60-minutes. As you are fully aware, neither the door nor window tests standard addresses temperature rise or radiant heat over the fire duration period. Enforcement officials and architects are being advised that, with 1-hour glass available for installation in a 1-hour wall, why settle for ¾ -hour glass? Further, where the Uniform Building Code limits the amount of glazing in a wall to 25% of the area involved, why not accept 40-50- or 60 percent since it is 1-hour glass? There are obvious answers as to why not but all building and fire officials are not that knowledgeable.

Another situation concerns just the code required 45-minute wired glass. The official is asked why accept 45-minute glass when he can require UL listed 1-hour non-wired glass? If 45-minutes is a minimum code requirement, why not require 60-minutes?

As a member of the NFPA Fire Council you may recall a question before the council as to the authority of NFPA 80 to impose limitations on the transmission of radiant heat through the glass. Whether this concern should originate with the Life Safety Code or NFPA 80 remains to be resolved.

To me, it borders on the ridiculous to require that a 1-hour corridor wall be limited to a temperature rise of 250ºF above the ambient and then permit 25% of the wall area to have glazing with no limitation on the amount of heat coming through it. Some years ago I conducted tests to determine at what temperature the heat transmitted through a stairway door would cause the use of a unit of exit width (22 inches) to be lost. It was determined that when there was a temperature rise of 450ºF above the ambient, that unit of exit width adjacent the door could no longer be used. That requirement is in the model codes. On that basis, plus the danger of transmitted heat igniting materials on the other side of the wall, it seems to me that allowing an additional 15-minutes of heat transference is improper.

This matter was discussed at the office of the Nevada State Fire Marshal and is the reason for this letter. The prevailing opinion seems to be that if UL lists the glass for 60-minutes, it may be good, and better, than the minimum code requirements. I don’t agree. I think that UL should re-examine it’s listing and add some additional wording on the label or some other method to avoid the misuse of a product.

Respectfully,

degenkob_signature

John G. Degenkolb

Share:
PrevNext ArticleOregon Forcing Wired Glass to meet CPSC Standards
Previous ArticleBill O’Keeffe’s Passionate Quest to Rid the Country of Wired GlassNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • sale@moishaglass.com
  • Representative Map
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
sale@moishaglass.com
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

AFFILIATE COMPANIES
Division 5
1850 Grogan Ave, Merced, CA 95341
888.653.3333
Division 8
1891 Wardrobe Ave, Merced, CA 95341
866.848.2667
© 2025 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}